Sprinkler5 min read

Frozen fire sprinkler pipes: where they happen and how to prevent them

How to prevent frozen fire sprinkler pipes: heat where the valves are, dry systems kept free of water, antifreeze tested, and cold spots found before winter.

Preventing frozen fire sprinkler pipes comes down to a few things done before the cold: heat in the rooms where the sprinkler valves are, the water emptied from the low points of dry systems, any antifreeze tested, and a look at the cold spaces that sprinkler pipe runs through. This is how a fire sprinkler system handles winter, where the cold reaches it, what gets done before the first freeze, and who to call if a pipe freezes.

How a fire sprinkler system handles the cold

A wet fire sprinkler system keeps water in its pipes all the time, so that pipe is kept at 40°F or warmer. Buildings that are heated year-round usually have wet systems.

Where a space cannot be kept that warm, such as unheated storage, a loading dock or an attic, it is usually protected by a dry system or an antifreeze system instead. A dry system's pipes hold compressed air, and the water stays below the dry valve, in a room that is kept heated. An antifreeze system's pipes hold an antifreeze solution in place of plain water. A pre-action sprinkler system also keeps air or nitrogen in its pipes, not water, until it is needed.

Converting part of a wet system to dry pipe for an unheated space is work we do on wet and dry fire sprinkler systems.

Where the cold reaches fire sprinkler pipe

Sprinkler pipe that holds water is at risk in the parts of a building where the heat doesn't reach. These are the places to look:

  • Entry vestibules and stairwells.
  • Attics, and the space around skylights.
  • Loading docks and unheated storage.
  • Spaces with little or no insulation.
  • Spaces that sit empty.

The rooms that hold the sprinkler valves get the same attention. On a dry system, the pipe below the dry valve holds water, so that room is kept at 40°F or warmer. In New Jersey, the fire code sets the same 40°F for sprinkler riser rooms and fire pump rooms, and calls for their heat to be permanently installed.

Outside the building, two pieces of equipment on the water supply are worth a look before winter. A dry-barrel fire hydrant is built to drain after it is used, so that water does not sit in it through the winter, and checking that it drains is part of fire hydrant testing. The backflow preventer on the fire sprinkler water supply can be damaged by freezing where it is exposed to the cold, and freeze damage is one of the backflow preventer repair jobs we do.

Water in a dry sprinkler system

A dry system's pipes are meant to hold air, but water still collects in them, from moisture in the compressed air and from the times the system has operated. It settles at the low points of the pipe, where small drains let it out. On a pre-action system, the low points have drains too.

Your fire sprinkler contractor drains those low points before the cold. NFPA 25, the code sprinkler systems are maintained to, also calls for them to be drained after the system operates, and as needed through the winter.

The air pressure matters too. If it drops too low, for example because the air compressor has stopped, the dry valve can open and fill the pipe with water, including pipe that runs through cold spaces. That is why the air pressure and the compressor are checked before winter as well.

Fire sprinkler system freeze prevention: what gets done before winter

Before the cold, these are the checks that get a fire sprinkler system ready:

  • Heat where the valves are. The rooms with the sprinkler valves, including the room with the dry valve and the fire pump room, are checked to make sure they hold 40°F or warmer (70°F for a room with a diesel fire pump that has no engine heater) and that the heater works.
  • Low-point drains. The water that has collected at the low points of dry and pre-action systems is drained.
  • Air pressure. On dry systems, the air pressure and the air compressor are checked.
  • Antifreeze. Samples are taken from the top and bottom of each antifreeze system and checked against the coldest temperatures expected in your area. If the solution no longer protects to that temperature, is mixed too strong, or its type cannot be identified, the system is drained and refilled with a factory-mixed antifreeze solution.
  • The cold spots. The cold spaces that sprinkler pipe runs through are looked over, so a fix, whether heat, insulation or a section of dry pipe, can be planned.

An antifreeze system should have a sign on its own valve that identifies the antifreeze in it, and the sign at the sprinkler riser should show whether there is an antifreeze system and where it is. An older system may not have these signs yet. Our article on fire sprinkler signs shows what the other signs are for.

A valve room can also have a low-temperature alarm connected to your fire alarm monitoring, so a room that is getting cold is reported.

Through the winter

Through the winter, the heat is what to keep an eye on: in the rooms where the sprinkler valves are, and in the spaces on the list above. A heater can stop working, and a broken window or a damaged roof can let cold air into a space with sprinkler pipe. The heat stays on in a building that sits empty, too.

If a fire sprinkler pipe freezes or bursts

Call your fire sprinkler contractor and tell them where the water is coming from, or where you think a pipe has frozen. Whether any part of the system should be shut off while the repair is arranged is a decision to make with us when you call. Our emergency line is answered around the clock.

Water expands as it freezes, and the pressure inside the pipe can crack it. The damage often does not show until the ice thaws, which is why a pipe you think has frozen is worth a call before anything leaks. Ice can also block the pipe, so the sprinklers beyond it may not get water until the pipe is thawed and repaired. Our article on a fire sprinkler leaking covers where leaks start and how they are repaired.

Our fire sprinkler winterization visit gets these checks done in one trip before the cold, across New Jersey, Pennsylvania and Delaware. Tell us which buildings and fire sprinkler systems you have, and we'll find a date that works for you.

Questions & Answers

Can fire sprinkler pipes freeze?

Yes. Pipe that holds water can freeze wherever the water in it gets cold enough, which is why water-filled sprinkler pipe is kept at 40°F or warmer. Spaces that cannot be kept that warm, such as unheated storage, loading docks and attics, are usually protected by a dry or antifreeze sprinkler system instead.

What temperature does a fire sprinkler valve room have to stay at?

40°F or warmer. In New Jersey, the fire code sets that minimum for sprinkler riser rooms and fire pump rooms and calls for their heat to be permanently installed. A room with a diesel fire pump that has no engine heater is kept at 70°F or warmer. On a dry system, the part of the dry valve that holds water is kept at 40°F or warmer as well.

What should be done to a dry fire sprinkler system before winter?

The water that collects at its low points is drained, the heat in the room with the dry valve is checked, and the air pressure and air compressor are checked. If the air pressure drops too low, the dry valve can open and fill the pipe with water.

How do I know if my fire sprinkler system has antifreeze in it?

Look at the sign at the riser, the vertical pipe where the system's main valves and gauges are. It should show whether there is an antifreeze system and where it is, and the antifreeze system's own valve should have a sign that identifies the antifreeze. An older system may not have these signs yet, and your fire sprinkler contractor can confirm it.

What should I do if a fire sprinkler pipe freezes or bursts?

Call your fire sprinkler contractor, tell them where the water is coming from or where you think a pipe has frozen, and decide with them whether any part of the system should be shut off while the repair is arranged. Damage from freezing often does not show until the ice thaws. Steele Services repairs frozen and burst fire sprinkler pipe across New Jersey, Pennsylvania and Delaware, and our emergency line is answered around the clock.