Skip to content
NJ · PA · DE
Steele Services — Fire Protection Specialists

Inspection & Testing · Installation · Maintenance

Portable Fire Extinguisher Service

Fire extinguisher inspection, placement, type, six-year internals and twelve-year hydrostatic tests — we handle it all and track every due date for you.

Extinguishers are the simplest system in the building and the easiest one to keep current. We run the whole program: the right extinguisher for the hazard, mounted at the right travel distance, and tagged on time.

Wall-mounted ABC portable fire extinguisher with a current inspection tag
ABC extinguisher · tagged and sealed
Standard
NFPA 10 — Portable Fire Extinguishers
Program
Annual maintenance, tags, internals, hydros
Types
ABC, CO₂, Class K, clean agent, D
Placement
Travel-distance surveys included
Recharge
After any discharge, same week
Coverage
NJ · PA · DE — statewide

Core services

Inspection and testing, installation, maintenance.

We schedule inspections, installations and repairs around your working hours, so your operation keeps running.

01

Annual Program

Every unit inspected, tagged and logged.

  • Annual maintenance and tagging on every unit
  • Monthly visual program — or we train your staff and leave the log
  • Placement and travel-distance survey against NFPA 10
  • Hazard-type matching — Class K at the fryer, CO₂ at the switchgear
  • All units on one report for the building
02

Internals & Hydros

The six-year internal maintenance and twelve-year hydrostatic test, tracked per unit.

  • Six-year internal examination on stored-pressure units
  • Twelve-year hydrostatic testing
  • Five-year hydros on water and wet chemical
  • Loaner units so coverage never lapses during testing
03

Supply & Recharge

New units, recharges and replacements, so nothing stays out of service waiting on a part.

  • New and replacement extinguishers supplied and hung
  • Recharge after discharge, same week
  • Bracket, cabinet and signage supply
  • Obsolete and condemned unit disposal

Service frequencies

Find the service frequencies your system requires.

The baseline below is what the code requires. Your local amendment or insurance carrier can require more.

NFPA 10

Portable Extinguishers

6Intervals

No.FrequencyRequired activityReference
01MonthlyRecorded visual inspection — pressure, access, seal§7.2
02AnnuallyMaintenance, verification and new tag§7.3.1
035 YearsHydrostatic test — water, AFFF and wet chemical§8.3.1
046 YearsInternal examination — stored-pressure dry chemical§7.3.6
0512 YearsHydrostatic test — dry chemical and CO₂§8.3.1
06On DischargeRecharge, verification of service and re-tag§7.8

Intervals shown are the NFPA baseline. Your local fire official or insurance carrier may require more. Read the standards free at NFPA.org (opens in a new tab)

Contact Us to Schedule Service

Common deficiencies

What actually fails inspection.

Extinguisher findings are the simplest to prevent — a monthly look and an annual service keep the whole program current.

Inherited a system?

We onboard systems installed by other contractors. First visit is an inventory and a condition report — priced, itemized, no surprises.

Contact Us
01

The wrong extinguisher for the hazard

An ABC unit next to a fryer will make a grease fire worse. We match the extinguisher to the hazard as part of the survey.

NFPA 10 §5.5

02

Six-year internal maintenance that has lapsed

A unit can carry ten consecutive annual tags and still be overdue for the six-year internal maintenance, which the tags do not record.

NFPA 10 §7.3.6

03

Units not returned to their proper place

Extinguishers get borrowed for a truck or moved for a pallet and never put back. The annual walk-through against a placement map shows which ones are missing.

NFPA 10 §7.2

Common Questions

Portable Extinguishers — questions we get asked.

Ask Us Directly
How often do fire extinguishers need to be inspected?

A monthly visual check, an annual maintenance inspection and tag by a certified technician, an internal examination at six years, and a hydrostatic test at twelve — intervals vary by extinguisher type.

What is the difference between the annual tag and the six-year service?

The annual is an external inspection and tag. The six-year internal requires emptying the extinguisher, inspecting it inside and recharging it. Both are required; only one is visible on the tag.

Do I have the right extinguishers in the right places?

Placement, travel distance and type are all specified per code, and they are among the most common things we correct — particularly K-class in kitchens and the right class near electrical equipment.

Can you manage extinguishers across multiple sites?

Yes. Multi-site extinguisher programs run on one calendar, with the reports for each building kept together.

What's on a fire extinguisher inspection checklist?

For the monthly visual: gauge pressure in range, nothing blocking access to the unit, and the pin and tamper seal intact — the three items code requires and expects logged. The annual adds a full maintenance check by a certified technician, a look at placement and travel distance against the hazard it protects, and a new tag.

We work on what's already in your riser room

AmerexAnsulBuckeyeBadger

No rip-and-replace pitch on the first visit. We hold current manuals and parts references for every line above — when a system genuinely can't be maintained any longer, we'll show you why before we quote a replacement.

Portable Fire Extinguisher Service in trouble right now?

Call 1-888-306-8430 — the line is answered around the clock by a technician who can access your system information and start guidance on the phone.